Measuring manifold pressure is not optional troubleshooting. It is the only reliable way to confirm that a gas fireplace is operating within its engineered combustion range.
Visual flame inspection alone cannot confirm:
This guide explains exactly how to measure manifold pressure, what the numbers mean, and how to interpret abnormal readings in real installations.
Manifold pressure is the regulated gas pressure delivered after the valve regulator and before the burner orifice.
It determines:
Manifold pressure is the final pressure that the burner sees.
Always verify with the manufacturer’s data plate or manual. These are typical reference values, not substitutes for specs.
Natural Gas:
Propane:
Operating outside these ranges will change flame behavior even if ignition appears normal.
You need one proper tool. Nothing else is acceptable.
Required:
Optional but recommended:
Never use:
Most gas valves include:
The manifold tap is usually a small slotted screw on the valve body marked “OUT” or “MAN”. Do not confuse it with the inlet pressure tap or pilot test ports.
Before connecting:
For sealed glass units like the Empire Rushmore 40 Direct Vent, refer to the manual regarding glass removal. Glass affects combustion and pressure behavior.
Ensure no other gas appliances are starting or stopping mid-test, and the thermostat is set to demand heat continuously.
Procedure:
Important: Do not remove the screw completely. Do not overtighten tubing adapters. A leaking test connection invalidates readings.
Turn the fireplace ON and allow:
Manifold pressure must be measured with the main burner operating—not during ignition or pilot-only operation. This is critical as pressure changes under heat load.
Observe steady pressure value and any fluctuation or pulsing. Record cold start pressure and warm stabilized pressure. Compare directly to manufacturer specification.
Possible causes: Undersized gas piping, inlet pressure too low, regulator not opening fully, excessive appliance demand elsewhere, or incorrect conversion components.
Symptoms: Weak flames, delayed ignition, flame dropout under load, reduced heat output.
This is a safety concern. Possible causes: Failed regulator diaphragm, incorrect regulator spring, wrong fuel regulator installed, or excessive inlet pressure.
Symptoms: Aggressive flames, flame lifting, overheating glass, burner noise, component damage. Do not adjust air shutters to compensate for high pressure.
Pressure instability indicates regulator failure, inconsistent supply, tank freeze-up (propane), undersized supply line, or appliance interaction issues. Fluctuation is never normal.
Some gas valves allow minor adjustment.
Rules:
Never: Modify regulators not designed for adjustment, drill or alter orifices to “fix” pressure, or adjust beyond factory limits.
After testing: Turn fireplace OFF, disconnect manometer, tighten tap screw snugly, and leak test the tap. Never leave a pressure tap loose.
A fireplace can ignite and still be improperly pressurized.
Proper pressure verification confirms correct installation, prevents soot complaints, reduces warranty claims, protects components, and ensures rated BTU delivery.
Many flame complaints disappear once pressure is corrected.
Manifold pressure measurement is not advanced troubleshooting. It is basic combustion verification.
If you do not measure it:
Every gas fireplace installation or service visit should include inlet pressure check, manifold pressure check, and flame observation under load. Anything less is incomplete work.